Central control module for creation of notification and evacuation control systems (SOUE) of 3 and 4 types. Fire control device in accordance with GOST R 53325-2009. It has a built-in amplifier 200W, a switchboard for 10 zones of notification, tangent microphone T-43, input signals GO, output for notification of on-duty personnel, LCD display, programmable 5 scenarios of notification, housing for installation in 19' Rack-rack.
Specifications
Number of fire alarm and activation inputs
10 pcs
Number of connected public address lines (not including duty personnel line)
2 pcs
Type of supported non-volatile memory (memory card types)
MMC, SD, SDHC
Maximum memory card capacity
32
Rated output power
200 W
Nonlinear distortion at rated output power, not more than
1 %
Line output voltage at rated output power
100 V
Amplifier bandwidth, 3 dB level
70...20000
Duty personnel line load capacity
10 W
Nominal signal level on line inputs
0.2 V
Input impedance rating for line inputs
600 ohm
Number of stages of microphone headset sensitivity adjustment
10 pcs
Number of stages of volume control in broadcast mode
10 pcs
Number of regulation steps independently for each zone
4 pcs
Number of contact groups for connection of fire evacuation actuators type ?? "dry contact"
2 pcs
Number of contact groups for connection of fire evacuation actuators of type NC "dry contact".
2 pcs
Switching load limit for switching on of fire evacuation actuators
5A, 240V
Switching load limit when switching on the external line of light boards
5A, 240V
Type of external contactor for activation of fire alarm inputs and triggering of CS notification
"dry contact"
Power consumption from 220 V power supply in standby mode, not more than
10
Power consumption from 220 V power supply in the mode of sound signal broadcasting, not more than
250
Rated voltage of the backup power supply
NZ-150-14,5 V
Current consumption from the backup power supply in the standby mode, not more than
0.2 A
Maximum current consumption from the backup power source
5 A
Open-circuit and short-circuit monitoring of input fire alarm loops, integrity monitoring of broadcast lines, connected
availability
The unit automatically switches to the backup power supply when the main power supply fails and automatically returns to the bac
availability
Resistance between the protective earth clamp and every metallic part of the device which can be touched.
0.1 ohm
Insulation resistance of power supply circuits from the earthed parts of the device, not less than
50 megohms ohm
Electrical insulation between mains circuits and earthed parts of the device withstands without breakdown for 1 m
1.5 kV Ampl.
Level of acoustic noises not more than
25 dBA
Designs of component parts of the device comply with the requirements of GOST 28601.3, and provides its installation in 19-inch
Compliance
Overall dimensions (length x height x depth) of the device components do not exceed
483 x 88.5 (2U) x 430 mm
Weight of the device does not exceed
10 kg
Assignment
Automatic control of speech warning and evacuation control system RECOR
Note: All specifications are provided by the manufacturer and may be subject to change. Please contact us to confirm the latest specifications before placing your order.
Share your requirements for a quick response!
Instant response in 15 minutes
Best wholesale prices guaranteed
Direct from manufacturer
Delivery & Payment
Shipping Terms
Delivery Time
Sea freight: 30-60 days (depending on destination) Air freight: 14-21 days (for urgent orders)
Payment Methods
Similar Products You May Be Interested In

Emergency Light Alarm LUIS+ L-24-2
View Details
Combined Fire Alarm (Light-Sound) LUIS+ L-12-2-SC
View Details
ARIA-PS-BR-R Expansion Module for Audio Signal Amplification
View Details
Fire Management Device S-KL for Emergency Communication
View Details
Dual-Sided Fire and Security Light Signal PRESTIGE-24 D
View Details
Voice Fire Alarm Speaker S-T-100V 1/3W MINI Version 2
View Details
Fire Alarm Light Indicator VOSKHOD-R-03
View Details
Fire Alarm Light M-24-ULTRA-MINI
View Details
Trombon PU-8K Control Device
View Details
Zone Control Console Expansion Module for Automatic Speech Notification RECHOR RPZU-30, RPZU-50, RPZU-70
View Details
Fire Control Device S-PU for Emergency Communication
View Details
Fire Alarm Voice Announcer Sonata-3 MINI
View DetailsVerified Suppliers
All products are sourced directly from authorized Russian manufacturers
Quality Assurance
Products meet international quality standards with proper certification
Global Shipping
Reliable logistics solutions to deliver products to your location
Secure Payments
Multiple secure payment options to facilitate international transactions