Addressable analogue combined fire | Russian Manufacturer | B2B

Description

The devices are designed to receive, process and display signals from fire detectors and other devices interacting with the devices, control the integrity and operation of communication lines, control executive devices of automatic fire protection equipment and control the integrity and operation of communication lines between devices and executive devices.

Specifications

Power supply from a DC source with voltage
24 V
Maximum number of RA-30 repeaters connected in series in one CAN line
4 pcs
Maximum length of the CAN interface, excluding repeaters
100 m
Supply voltage of remote control valves, OZK valves
220 V
Number of controllers connected to the control panel via CAN interface
32 pcs
Maximum length of the CAN interface, including repeaters
500 m
Number of valves to be connected
2 pcs
Own current consumption in standby mode
Not more than 0.22 A
Own current consumption in "Fire" mode
Not more than 0.32 A
Communication interface
CAN, RF 868 MHz, RS-485, PLC, Wi-Fi
Number of occupied addresses in the CAN network
1 pcs
Number of RS-485 interfaces
2 pcs
Maximum interface length between RS-485 segments
100 m
Number of PLC interfaces
2 pcs
Maximum PLC load current per channel
0.35 A
Maximum length of the PLC interface
3000 m
Number of addressable devices connected to the control panel via PLC and RF 868 MHz interface
250 pcs
Operating frequency of the radio channel interface
868
Number of channels within the frequency range
5 pcs
Channel encryption
XTEA 128bit
Radiation power
Not more than 25 mW
Maximum communication range between CCPs and radio-channel ODRs via RF 868 MHz interface, in open terrain
900 m
Types of valves to be connected
Electromagnetic, Reversible, With return spring
Number of freely programmable inputs
2 pcs
Maximum voltage at the freely programmable input
20 V
Maximum line monitoring current of a freely programmable input
0.005 A
Number of controlled dry contact outputs
2 pcs
Maximum voltage at the SC output
220 V
Maximum switched current at the "Dry contact" output
2 A
Number of outputs with line open-circuit and short-circuit monitoring
2 pcs
Output voltage
24 V
Maximum switched current at each output "OUT1" and "OUT2"
0.45 A
Operating frequency of the Wi-Fi interface
2400
Maximum communication range (in open terrain)
SBVVBG m
Operating temperature range
-10...55 °C
Relative humidity at + 40 deg. ?
0...93 %
Degree of enclosure protection
IP20
Dimensions (L x W x H), mm
245 x 197 x 32
Weight
0.7 kg
Average service life
10 year
Average MTBF
60000
Probability of failure-free operation in 1000 h
0.98

Note: All specifications are provided by the manufacturer and may be subject to change. Please contact us to confirm the latest specifications before placing your order.

Save Your Time

Share your requirements for a quick response!

Instant response in 15 minutes
Best wholesale prices guaranteed
Direct from manufacturer

Delivery & Payment

Shipping Terms

FOB Novorossiysk, Russia CIF Available to major ports worldwide EXW Manufacturer's facility, Russia

Delivery Time

Sea freight: 30-60 days (depending on destination) Air freight: 14-21 days (for urgent orders)

Payment Methods

Letter of Credit (L/C) Wire Transfer (T/T) Escrow Services

Similar Products You May Be Interested In

Verified Suppliers

All products are sourced directly from authorized Russian manufacturers

Quality Assurance

Products meet international quality standards with proper certification

Global Shipping

Reliable logistics solutions to deliver products to your location

Secure Payments

Multiple secure payment options to facilitate international transactions

Your callback request has been received. We'll contact you shortly.